March 30, 2000

Mr. & Mrs. ABC
123 Old Street
Toronto, ON

RE: 123 Old Street, Toronto, Ontario

An inspection was performed at the above captioned address on May 25th, 1999. The objective of the inspection and this report is to provide pertinent information which would be of concern to a prudent buyer in making their decision to purchase a property. Maintenance and repair requirements are prioritized.

It is to be noted that our inspection was principally associated with the structural and operational function of the premises and does not necessarily cover matters of a "cosmetic" nature. The required repairs to the dwelling include, but are not limited to, what is purported herein due to the limitations of the visual inspection. The report remains the opinions of Baker Street Home Inspection Services Inc.

The dwelling located at 123 Old Street, Toronto is a solid masonry structure and is approximately 70 - 75 years old. The premise has been substantially renovated approximately 20 years ago. The house has been renovated with skilled workmanship and good quality building materials.

During the course of the inspection there were no major defects observed that would compromise the safe habitability of the dwelling (as a whole) over the next 3-5 years.

Roofing Systems

The building has been constructed with a hip type roof. The roof surface is covered with asphalt shingles which were found to be in poor general condition. There should be approximately two years of functional life remaining on the roof shingles. There is approximately five years of functional life remaining on the garage roofing shingles. The flat roof at the rear addition flat roof is in very good condition. All roof joints and flashings appear to be in fair overall condition. Please be advised that maintenance or a roof tune-up is recommended prior to the next shingle application.

The eavestroughs and downpipes are made of aluminum and are in good overall condition. The downpipe extension at the rear (north-west) corner is damaged and should be replaced. Due to the close proximity of trees a semi-annual removal of leaves from the eavestroughs is recommended. The tree branches at the north-west corner should also be pruned in the near future.

The soffit and facia have been faced with aluminum and are both in good condition. The rear addition skylights are in good condition. Periodical maintenance is recommended at the flashing joints.

General Exteriors

The masonry chimneys (at the east of the dwelling) require repair. Replacement of the flashing (to be done with new shingles) and new chimney caps are also recommended.

The exterior wall assembly is generally termed as solid masonry; the wall is constructed with a full inner and outer course of brick. The brick units and the mortar joints are in very good overall condition. There is very minor brick deterioration at the south-west corner. This can be repaired at the same time as the chimney work.

The upper level is comprised of a stucco wall covering. General painting of the stucco is recommended in the near future.

The predominant windows are casement and horizontal sliding double glazed units in aluminum frames. The main floor and second floor units are in good condition. Frame repair and painting is recommended to the third floor dormer window units. Replacement of the west basement windows is recommended.

The main entrance door systems are in good condition. The rear garage door and door sill should be repaired in the future.

In general, the grading or soil/walkway conditions adjacent to the building appear to favourably channel rain water away from the foundation. Improper grading is the most common reason for leaking basements. However, the patio stones at the west slope towards the house. The grade should be reworked to channel water away from the foundation wall.

Shallow window well(s) should also be installed at this area. Some rot is developing in rear garden retaining walls. Replacement of a few lengths of 6" x 6" is recommended.

The single car detached garage is in fair overall condition. Eavestroughs are recommended to be installed. The wood overhead garage door is cumbersome and could be adjusted for easier use.

The lower wood deck at the rear of the dwelling is in good overall condition. The decking, stair system and railing assembly have been constructed in a good workmanlike manner.

The balcony guards rails are defective and require replacement. The existing guard rails are only 3 feet in height. The new guards should be 42" in height.

There is a garden hose connection at the rear of the dwelling. Garden fencing and gates are in good condition.

Electricity is provided to the building by an overhead service entrance or service drop system. The weather head, mast and conduits are all firmly affixed to the building signifying proper installation. All entrances are illuminated and the front and rear light fixtures are in good condition. Replacement of the side entrance light fixture is recommended. There is a functional exterior duplex receptacle at both front and rear of the house. However, these receptacles should be replaced with ground fault circuit interrupters.

The swimming pool was not open and accessible for inspection. Any information regarding the age and function of the pool should be obtained from the pool service company.

Electrical System

The main electrical service is a 200 ampere 120/240 VAC system. The service and distribution panels are relatively new and are in good condition. The main disconnect and all circuit overload protection devices are circuit breakers. There are approximately four spare circuits available at the main distribution panel for future home improvements and electrical additions.

All branch wiring in the house is copper (Romex 14-2 with ground).

There is a good number of electrical plugs in the finished spaces of the dwelling. Curiously, one electrical receptacle did not function under the dining room window. The wiring connection for the kitchen stove should also be reworked. All bathroom plugs require to be replaced with ground fault circuit interrupter (safety receptacles.) There is a light fixture with control switch in each finished space of the dwelling.

A powered attic ventilator is recommended to be installed within the heat gain during the hot summer months.

Plumbing System

The main shut-off valve is located at the front of the basement and is in functional condition.

All branch water lines are copper and adequate pressure is provided to each plumbing fixture. All drain, waste and vent pipes were found to be ABS (type, plastic) and no abnormal drainage conditions were found.

All plumbing fixtures and fittings were operated and were found to be in operational order. There is good flow and pressure being provided to each floor level. The hot water tank is an electric controlled unit and is rented from the local utility.

Central Heating System

Heat is being provided to each habitable space by electric radiant baseboard heaters. All baseboard heaters were tested at the time of inspection and were found to be functional. One heating unit in the laundry room is loose and requires fastening to the wall.

Electrical baseboard heaters are not the preferable heating system type for homes in Toronto. However, since each unit has a separate control, a multi-zoned heating system is realized. The positive aspects of a multi-zoned heating system is that zones not commonly used or needed may be kept at lower temperatures.

The installation of 3-speed reversible ceiling fans centrally located will help reduce heating costs in the winter. Not only will the fan paddles push the heat back down from the ceiling but increased air circulation will result in even temperature distribution. The fans also have an added cooling effect during the summer months.

It is suggested that the most cost effective retrofit recommendation would be the installation of a forced-air high- efficiency gas furnace with at least one supply outlet in each second and third floor room and one return air vent at each floor level. The furnace could be installed in the attic space or a roof mounted unit could also be considered. The new air duct system could be arranged so that certain main floor areas are serviced. A portion of the existing main floor heaters and all basement heaters would remain. The new air duct system would readily accommodate central air conditioning. This proposed retrofitting concept should not exceed $12,000.

General Interiors

All structural members were found to be in good overall condition at the time of inspection. There was no evidence of any leaking or water penetration through the foundation wall.

The addition at the rear is supported by masonry columns and wood beams. It is recommended that all debris be removed from the crawlspace. A moisture barrier and ground cover should be installed to the crawlspace floor. Insulating the exterior perimeter walls will help comfort levels in winter. As this family room is not above a heated basement it is expected that maintaining total comfort will be difficult during extremely cold days.

The interior wall finish has been mostly constructed with gypsum board (drywall). All wall and ceiling finishes were found to be in good overall condition.

All floor finishes of the first and second levels were found to be in good condition (i.e. carpet, ceramic tile, oak strip flooring, etc.)

All windows were tested and were found to be in operational and in good overall condition.

All doors were tested and were found to be in good overall condition. New guide wheels are required to be installed at the rear patio door. Minor adjustment is required to the master ensuite door.

The primary and basement stair systems are properly constructed, safe and offer very good headroom and lateral clearances for the moving of furniture. However, the spiral staircase to the third floor provides limited clearance. A handrail is recommended to be installed to the basement staircase.

Additional thermal insulation installed to the attic floor is recommended. However, if this is carried out, increased ventilation into the roof space at the eaves or lower portion of the roof is essential.

The masonry fireplace in the living room is in good overall functional condition. The flue is recommended to be cleaned. It is important to note that the fireplace in the south-east bedroom could be reclaimed.

All bathrooms in the dwelling are in good overall condition. All plumbing fixtures and accessories are functional. All bathrooms are adequately ventilated. Silicone and grout touch-ups are recommended in the basement bathroom and the master ensuite. A new shower head is required in the master ensuite and second floor main bathroom. The third floor sink is loose and should be fastened to the wall. The main bathroom wash basin is chipped and should be replaced in the future.

Baker Street Home Inspection Services Inc. performs all inspections of real property within the prescribed "Code of Ethics" and "Standards of Practice" of the American Society of Home Inspectors (ASHI) and The Ontario Association of Home Inspectors.

Every effort has been made to provide this report with the most accurate and practical information for the purpose intended. This report will not cover third party indemnification unless the writer has the opportunity to provide the prospective purchaser with on-site orientation.

Please do not hesitate to call if the reader requires further information or clarification.

Sincerely,
BAKER STREET HOME INSPECTION SERVICES INC.



J. Clarke, CET
Registered Home Inspector

Baker Street Home Inspection Services Inc.
In operation since 1985

Serving the Greater Toronto Area from
Oakville to the west, Newmarket to the
north and Oshawa to the east.
3335 Yonge Street, Suite 402
Toronto, Ontario, M4N 2M1

Tel - (416) 483-3535
Fax - (416) 483-9756
info@bakerstreet-hi.ca
Regular Business Hours (Monday to Friday)
8:30 am to 12:30 pm
1:30 pm to 4:30 pm

Our phones are monitored
continuously after business hours.